Skip to content
EWAD-TZSSD Daikin

EWADC10TZSSD2

Air-cooled screw inverter chiller EWADC10TZSSD2.

Operating mode
Cooling
Cooling capacity
1017 kW
Serviced area
8475 m²
Number of circuits
2
All characteristics
Price
On request
Send a request: the manager will select the configuration and send you a commercial offer.
To order
Operating modeCooling
Cooling capacity1017 kW
Serviced area8475 m²
EER3,1
Dimensions (H×W×D)2553×2238×7960 mm
Weight6623 kg
Performance ControlStepless
Compressor typeScrew
Number of circuits2
Evaporator typeShell and tube
Capacitor typeAir
Energy consumption (cooling)332.2 kW
Operating temperature range - water (cooled)4~18°C
Operating temperature range - air (cooled)-20~46 °C
Sound power level100 dBA
Sound pressure level79 dBA
Power supply3~/50/400 (Phase/Hz/V)
RefrigerantR-134a
Refrigerant charging140 kg
Water inlet/outlet size (Evaporator)219.1 mm
BrandDaikin
SeriesEWAD-TZSSD
ModelEWADC10TZSSD2
Guarantee5 years

Air-cooled screw inverter chiller EWADC10TZSSD2. SILVER efficiency.

● Environmentally friendly HFC134a – the most thermodynamically efficient refrigerant for air-cooled systems;
● The EWAD-TZSSD series chillers are equipped with a new generation of air-cooled inverters and a wide performance range from 280 kW to more than 2 MW: the rated power of the EWADC10TZSSD2 chiller is 1017 kW;
● For reliability and maximum safety during maintenance, the chiller is equipped with two independent refrigeration circuits;
● Standard noise level;
● New single-screw compressor geometry to optimize performance;
● Refrigerant-cooled inverter mounted on the compressor;
● Premium energy efficiency at both full and part load;
● Best performance with minimal footprint;
● Microchannel coils;
● Unique fully integrated solution for active harmonic filtering;
● Performance monitoring;
● MicroTech 4 Controller: Sophisticated adaptive software logic maintains stable operating conditions.

Daikin Product Catalog PDF Open
Technical data sheets, installation instructions and certificates are available upon request.

Installation is carried out by DC Engineering's own certified teams: engineer visit, selection of routes, commissioning and commissioning in compliance with the requirements of the manufacturer and SNiP.

Official Daikin service center: warranty up to 5 years, scheduled maintenance, diagnostics and repairs of any complexity, original spare parts from stock.